Air-handling unit fanB3P355-EC188-024
B3P355-EC188-024 is an AFL air-handling unit fan in the published model records. Review its documented specifications, installation requirements and source information against your equipment duty.

Review the documented model data
Supply: 3x400 VAC. Frequency: 50/60 Hz. Power input: 3100 W. Speed: 3800 rpm. Control input: 0-10 VDC / PWM. The AFL catalogue lists 3x400 VAC, 50/60 Hz, 3100 W for this air-handling unit fan. Check the 0-10 VDC / PWM control interface against your controller. The catalogue enclosure rating is IP44.
Check the installation and operating point
Define the airflow and static pressure required by the air-handling equipment. Include filters and coils in the system resistance and check installation and service access against the drawing.
Match the electrical interface
Confirm the supply and the exact speed-control and feedback interface required by the equipment controller. An EC designation alone does not establish the supported control signal.
Use the technical documents
Check the attached model documents and their page references before sample evaluation. Confirm the complete suffix and document revision. Performance at your required duty point must be checked on the corresponding curve.
Discuss this model
Include B3P355-EC188-024, required airflow and static pressure, power supply and available installation space in your inquiry. Attach the equipment layout and identify any required control or feedback signals.
EC fans and blowers · AHU fans
Specifications
- Model
- B3P355-EC188-024
- Drive
- EC
- Supply
- 3x400 VAC
- Frequency
- 50/60 Hz
- Current draw
- 5.2 A
- Power input
- 3100 W
- Speed
- 3800 rpm
- Control input
- 0-10 VDC / PWM
- Sound pressure level
- 96 dB
- Degree of protection
- IP44
- Working temperature
- -25 ~ +60 °C
- Insulation class
- F
- Impeller material
- sheet aluminium
Manufacturer catalogue pages
Check the drawing and rated conditions for the complete model.
Catalogue page 141Selection from the source sheet
Air-handling units. Presentation slide 27 lists 3,500 m³/h at 1,800 Pa. Confirm the test arrangement and proposed revision for your equipment.
| Airflow (m³/h) | Static pressure (Pa) |
|---|---|
| 3500 | 1800 |
| 3000 | 2100 |
| Catalogue field | Value on this page |
|---|---|
| Supply | 3x400 VAC |
| Frequency | 50/60 Hz |
| Current draw | 5.2 A |
| Power input | 3100 W |
| Speed | 3800 rpm |
| Control input | 0-10 VDC / PWM |
| Sound pressure level | 96 dB |
| Degree of protection | IP44 |
| Working temperature | -25 ~ +60 °C |
| Insulation class | F |
| Impeller material | sheet aluminium |
Related documents and engineering decisions
FFU, data centre and AHU engineering presentation · p. 27 EC backward-curved centrifugal fan catalogue · p. 44Equipment fit and selection
For air-handling equipment, specify airflow together with static pressure, mounting space and speed control. Confirm the selected suffix against the equipment drawing.
Equipment selection guide What to check before ordering Factory and qualification documentsRelated models to review
Compare the complete suffix, mounting and operating conditions before specifying a replacement.
Framed B400 configuration · AFL equipment presentation, slide 25.B3P400-EC188-031B3P400-EC188-031: review air-handling unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
Framed B400 configuration · AFL equipment presentation, slide 25.B3P400-EC188-032B3P400-EC188-032: review air-handling unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
B450 impeller illustration · AFL equipment presentation, slide 26.B3P450-EC188-951B3P450-EC188-951: review air-handling unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.Related resources and guides
Framed B400 fan for AHU review · AFL equipment presentation, slide 25.ApplicationsAir-handling unitsReview a centrifugal fan for an air-handling unit against the full equipment duty point and the space available for service.
EC backward-curved centrifugal fan catalogue · source previewTechnical resourcesEC backward-curved centrifugal fan catalogueUse the full EC fan designation to locate the curve, control wiring and installation drawing.
FFU, data centre and AHU engineering presentation · source previewTechnical resourcesFFU, data centre and AHU engineering presentationApplication-specific models, paired duty points, controller configurations and equipment-level test examples.