FFU, data centre and AHU engineering presentation
Application-specific models, paired duty points, controller configurations and equipment-level test examples.

How to read this document
Slides 4–13 cover FFUs; slides 15–22 cover data centre cooling; slides 23–27 cover AHUs. Preserve the tested assembly and duty point when requesting a comparable result.
Related documents and engineering decisions
All manufacturer documents Selection guide Cleanroom fan filter units (FFUs) Data centre cooling: in-row units and fan walls Air-handling units B3P325-EC102-001 B3P426-EC102-001 B3P456-EC102-007 B3P456-EC137-001Download original PowerPoint (28 slides)
Page index
Use the original drawing for tolerances, suffixes and performance values.
- Slide 1 · Cover
- Slide 2 · FFU group control
- Slide 3 · Project references
- Slide 4 · 2 × 4 FFU variants · B3P310-EC092-016 · B3P310-EC092-019 · B3P310-EC092-045 · B3P310-EC092-040 · B3P310-EC092-041 · B3P325-EC102-002
- Slide 5 · 4 × 4 FFU variants · B3P456-EC102-007 · B3P400-EC102-048 · B3P400-EC102-065 · B3P400-EC102-067 · B3P400-EC102-070 · B3P400-EC102-075 · B3P400-EC102-095 · B3P400-EC102-096
- Slide 6 · B325 FFU duty · B3P325-EC102-001
- Slide 7 · B426 FFU duty · B3P426-EC102-001
- Slide 8 · B456 FFU duty · B3P456-EC102-007
- Slide 9 · FFU test configuration
- Slide 10 · Insulated shaft
- Slide 11 · Controller and network
- Slide 12 · Assembly test: B456
- Slide 13 · Assembly test: B426
- Slide 14 · Data centre and AHU overview
- Slide 15 · Electrical input families
- Slide 16 · In-row fan: B456 · B3P456-EC137-001
- Slide 17 · Fan wall: B640 · B3P640-EC188-901
- Slide 18 · Compact in-row fan: B225 · B3P225-EC072-008
- Slide 19 · In-row EC fan: A500 · A3P500-EC102-008
- Slide 20 · Compact DC fan: A180 · A3P180-DC092-002
- Slide 21 · DC panel fan: A200 · A3P200-DC072-027
- Slide 22 · Enclosed DC fan: B225 · B3P225-DC072-903
- Slide 23 · AHU operating-point matrix
- Slide 24 · B456 paired duties · B3P456-EC137-950
- Slide 25 · B400 bare and framed variants · B3P400-EC188-031 · B3P400-EC188-032
- Slide 26 · B450 AHU duty points · B3P450-EC188-951
- Slide 27 · B355 high static pressure · B3P355-EC188-024
- Slide 28 · Closing slide
Slide 1 · Cover
Enlarge drawing or table · Open original file

Slide 2 · FFU group control
Enlarge drawing or table · Open original file

Original slide text
FFU智能群控系统解决方案 http://www.hzafl.com
Slide 3 · Project references
Enlarge drawing or table · Open original file

Original slide text
FFU用风机重要项目 1 1. 世界先进集成电路股份有限公司(tsmc 相关公司) 2. 采钰科技股份有限公司(tsmc 相关公司) 3. 美商英特格有限公司台湾分公司 4. 大立光电股份有限公司 5. 达兴材料股份有限公司 6. 环球晶圆股份有限公司中德分公司 7. 南亚电路板股份有限公司 8. 台虹科技股份有限公司 9. 合晶科技股份有限公司 10. 南美特科技股份有限公司 11. 友达光电股份有限公司 12. 致茂电子股份有限公司 13.江苏威达建设有限公司 14.中建三局第一建设工程有限责任公司 15.中建三局第一建设工程有限责任公司 16常州市骏诺建材商贸有限公司 17.陕西推摺西风行万合建筑工程有限公司 18.科越工程(苏州)有限公司 19.中国电子系统工程第四建设有限公司 20.信息产业电子第十一设计研究院科技工程股份有限公司 20.淮安市康嘉实业有限公司 21.重庆惠科金渝光电科技有限公司 22.广州华星光电半导体显示技术有限公司 23.盟立自动化科技(上海)有限公司 24.通彩智能科技集团有限公司 25.天通吉成机器技术有限公司 累计出货量:超50万台
Slide 4 · 2 × 4 FFU variants · B3P310-EC092-016 · B3P310-EC092-019 · B3P310-EC092-045 · B3P310-EC092-040 · B3P310-EC092-041 · B3P325-EC102-002
Enlarge drawing or table · Open original file

Original slide text
2*4 FFU风机量产机型 2 · FFU 2*4机型用标准风机系列: 1. B3P310-EC092-016(L137) 带HALL 陶瓷涂层轴 2. B3P310-EC092-019(L137) 带HALL 常规轴 3. B3P310-EC092-045(L137) 无HALL 陶瓷涂层轴 4. B3P310-EC092-040(L107) 无HALL 常规轴 5. B3P310-EC092-041(L107) 带HALL 常规轴 6. B3P325-EC102-002 带HALL 陶瓷涂层轴
Slide 5 · 4 × 4 FFU variants · B3P456-EC102-007 · B3P400-EC102-048 · B3P400-EC102-065 · B3P400-EC102-067 · B3P400-EC102-070 · B3P400-EC102-075 · B3P400-EC102-095 · B3P400-EC102-096
Enlarge drawing or table · Open original file

Original slide text
4*4 FFU风机量产机型 3 · FFU 4*4机型用标准风机 1. B3P400-EC102-048(L142) 带HALL 陶瓷涂层轴 2. B3P400-EC102-065(L142) 带HALL 常规轴 3. B3P400-EC102-067(L162) 带HALL 陶瓷涂层轴 4. B3P400-EC102-070(L162) 无HALL 陶瓷涂层轴 5. B3P400-EC102-075(B456) 带HALL 陶瓷涂层轴 6. B3P456-EC102-007(B456) 无HALL 常规轴轴 7. B3P400-EC102-095(B426) 内置驱动485 8. B3P400-EC102-096(B456) 内置驱动485
Slide 6 · B325 FFU duty · B3P325-EC102-001
Enlarge drawing or table · Open original file

Original slide text
FFU用高效率B325
4
· 概述:采用螺旋式双曲面5叶片混流式离心风轮、形成低风阻、高效率、超薄结构。
(最高整机静压效率约61%以上,)
· 额定工作点:
静压200PA 风量1150m3/h
· 机种名:B3P325-EC102-001
· 总高度:158mmSlide 7 · B426 FFU duty · B3P426-EC102-001
Enlarge drawing or table · Open original file

Original slide text
FFU用高效率B426
5
· 概述:采用螺旋式双曲面5叶片混流式离心风轮、形成低风阻、高效率。
(最高静压效率约66.5%,提高约9个百分点)
· 额定工作点:
静压300PA 风量2400m3/h 1500RPM
· 机种名:B3P426-EC102-001
· 总高度:206mmSlide 8 · B456 FFU duty · B3P456-EC102-007
Enlarge drawing or table · Open original file

Original slide text
FFU用高效率B456
6
· 概述:采用螺旋式双曲面5叶片混流式离心风轮、形成低风阻、高效率。
(最高静压效率约68%,提高约10个百分点)
· 额定工作点:
静压300PA 风量2940m3/h
· 机种名:B3P456-EC102-007
· 总高度:246mmSlide 9 · FFU test configuration
Enlarge drawing or table · Open original file

Original slide text
FFU用高效率B456 7 · 测试风机:B3P456-EC102-007 / 德国某公司波浪形塑胶风轮B400 · 测试地点:艾弗洛实验室 · FFU机器:台湾客户整机
Slide 10 · Insulated shaft
Enlarge drawing or table · Open original file

Original slide text
FFU风机用陶瓷绝缘轴
8
· 概述:针对FFU行业客户的特殊要求,我们从2016年开始研究高温烧结陶瓷在
电机上的应用,经历3年不断测试和改进,替代了陶瓷球轴承。
特点:相比树脂绝缘材料涂层,陶瓷涂层具体高强度且不易磨损。
(2019年开始实现批量生产,至今使用批量超过40万支。)
陶瓷涂层
· 机种名:适用全系列直流无刷风机Slide 11 · Controller and network
Enlarge drawing or table · Open original file

Original slide text
FFU风机用控制器
9
· 概述:针对FFU行业客户的整体配套要求,研发成功FFU专用控制器
· 机种名:适用350W以下直流无刷风机
1.风机控制器
2.路由器
3.上位机软件(可集中控制6万台)Slide 12 · Assembly test: B456
Enlarge drawing or table · Open original file

Original slide text
FFU整机第三方测试 10 · 台湾AAF机器:艾弗洛EC102(B456) 最高效率61.3%
Slide 13 · Assembly test: B426
Enlarge drawing or table · Open original file

Original slide text
FFU整机第三方测试 11 · 江苏富泰机器:艾弗洛EC102(B426) 最高效率65.4%
Slide 14 · Data centre and AHU overview
Enlarge drawing or table · Open original file

Original slide text
数据中心及AHU高效风机解决方案 http://www.hzafl.com
Slide 15 · Electrical input families
Enlarge drawing or table · Open original file

Original slide text
数据中心用高效风机 1 数据中心用高效风机系列: ·AC380V输入750W EC137的后倾456风机 ·AC380V输入1.7KW EC137的后倾456风机 ·AC380V输入5.5KW EC188的后倾640风机 ·AC220V输入170W EC72的后倾225风机 ·AC220V输入500W EC102的轴流490风机 ·DC48V输入100W DC072的后倾225风机 ·DC48V输入550W DC102的轴流300风机 ·DC48V输入300W DC102的轴流450风机 ·DC48V输入300W DC072/ 550W DC092的轴流180风机
Slide 16 · In-row fan: B456 · B3P456-EC137-001
Enlarge drawing or table · Open original file

Original slide text
数据中心用高效风机
2
· 概述:采用螺旋式双曲面5叶片混流式离心风轮、形成低风阻、高效率。安装尺寸相同条件下,
风机性能显著提升。
· 额定工作点:
静压350PA 风量4850m3/h
· 列间空调/恒湿机用风机:B3P456-EC137-001Slide 17 · Fan wall: B640 · B3P640-EC188-901
Enlarge drawing or table · Open original file

Original slide text
数据中心用高效风机
3
· 概述:采用螺旋式双曲面5叶片混流式离心风轮、形成低风阻、高效率。
(最高静压效率约68%)
· 额定工作点:
静压1080PA 风量12460m3/h
· 风墙末端用风机:B3P640-EC188-901Slide 18 · Compact in-row fan: B225 · B3P225-EC072-008
Enlarge drawing or table · Open original file

Original slide text
数据中心用风机 4 · 概述:300列间侧出风定制混流式叶轮235,最高效率50% · 额定工作点: 静压420PA 风量840m3/h · 300列间空调用紧凑型EC风机:B3P225-EC072-008
Slide 19 · In-row EC fan: A500 · A3P500-EC102-008
Enlarge drawing or table · Open original file

Original slide text
数据中心用高效风机
5
· 概述:薄型塑胶框体及混流式叶轮设计,实现低风阻、大风量、
高效率。(最高静压效率51%)
· 额定工作点:
静压190PA 风量4000m3/h
· 600列间空调用EC风机:A3P500-EC102-008Slide 20 · Compact DC fan: A180 · A3P180-DC092-002
Enlarge drawing or table · Open original file

Original slide text
数据中心用风机 6 · 概述:小型化(200mm*200mm)、高静压、大风量 · 额定工作点: 静压750PA 风量1160m3/h · 300列间空调用紧凑型DC风机:A3P180-DC092-002 (DC48V)
Slide 21 · DC panel fan: A200 · A3P200-DC072-027
Enlarge drawing or table · Open original file

Original slide text
数据中心用风机 7 · 概述:超薄型、低噪音、大风量 · 额定工作点: 静压65PA 风量1100m3/h · 面板列间风机:A3P200-DC072-027 (DC48V) 尺寸:235*235*65 mm
Slide 22 · Enclosed DC fan: B225 · B3P225-DC072-903
Enlarge drawing or table · Open original file

Original slide text
数据中心用高防护风机
8
· 概述:针对室外防护等级高要求,采用BMC成型和全封闭式结构设计,实现防护
等级IP68
· 额定工作点:
静压540PA 风量690m3/h
· 定制款高防护风机:B3P225-DC072-903 (DC48V)Slide 23 · AHU operating-point matrix
Enlarge drawing or table · Open original file

Original slide text
AHU用风机系列 9 静压 风量 风机型号 Pa m3/h 1000 4000 B3P400-EC137-952/953(456mm) 1000 8000 B3P400-EC188-031/032(450mm) 1300 6000 1000 12500 B3P630-EC188-900/911(640mm) 1200 12500 B3P450-EC188-950/951(B540) 1600 9000 1800 3500 B3P355-EC188-024 2100 3000
Slide 24 · B456 paired duties · B3P456-EC137-950
Enlarge drawing or table · Open original file

Original slide text
紧凑型高性能后倾B456
10
· 概述:采用螺旋式双曲面5叶片混流式离心风轮、形成低风阻、高效率。安装尺寸相同条件下,
风机性能显著提升。
· 额定工作点:
静压900PA 风量5000m3/h
静压1000PA 风量4000m3/h
· 机种名:B3P456-EC137-950Slide 25 · B400 bare and framed variants · B3P400-EC188-031 · B3P400-EC188-032
Enlarge drawing or table · Open original file

Original slide text
高效率后倾风机B400
11
· 概述:采用螺旋式双曲面5叶片混流式离心风轮、形成低风阻、高效率。
(最高静压效率约63%)
· 额定工作点:
静压1000PA 风量8000m3/h
静压1300PA 风量6000m3/h
· 机种名:B3P400-EC188-031(仅风机)/032(带框体)Slide 26 · B450 AHU duty points · B3P450-EC188-951
Enlarge drawing or table · Open original file

Original slide text
AHU用后倾B450 12 · 概述:采用螺旋式双曲面5叶片混流式离心风轮、形成低风阻、高效率,最高静压效率63%。 · 用途:AHU等通风设备 · 额定工作点: 静压900PA 风量15000m3/h 静压1300PA 风量12000m3/h 静压1600PA 风量10000m3/h · 机种名:B3P450-EC188-951(最大540mm)
Slide 27 · B355 high static pressure · B3P355-EC188-024
Enlarge drawing or table · Open original file

Original slide text
高静压后倾B355
13
· 机种名:B3P355-EC188-024
· 概述:采用螺旋式双曲面5叶片混流式离心风轮、形成低风阻、高效率。安装尺寸相同条件下,
风机性能显著提升。
· 额定工作点:
静压1800PA 风量3500m3/h
静压2100PA 风量3000m3/hSlide 28 · Closing slide
Enlarge drawing or table · Open original file

Original slide text
Thanks ! 智 能 Intelligence 高 效 High Efficiency 低噪音 Low Noise
Engineering guides
AFL product family illustration · axial fan. Individual mounting and accessories vary by suffix.What should I ask when two suppliers quote different selection points?First align the units and confirm whether both proposals quote static or total pressure. Check that each refers to the same assembly and control setting.
2 × 4 fan filter unit · AFL equipment presentation, slide 4.Which FFU fan and controller combination should I specify?For the same FFU size, the presentation lists different Hall feedback, shaft and drive configurations.
In-row cooling equipment · AFL equipment presentation, slide 16.Which duty point applies to a fan wall or an in-row cooler?Compare paired pressure and flow values for the equipment arrangement you are buying.
Framed B400 fan for AHU review · AFL equipment presentation, slide 25.How should I quote an AHU fan at two operating points?State each airflow together with its static pressure and keep bare and framed variants separate.Relevant product families
FFU assembly · AFL equipment presentation, slide 6.B3P325-EC102-001B3P325-EC102-001: review fan filter unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
B426 impeller · AFL equipment presentation, slide 7.B3P426-EC102-001B3P426-EC102-001: review fan filter unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
B456 impeller · AFL equipment presentation, slide 8.B3P456-EC102-007B3P456-EC102-007: review fan filter unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
B3P456-EC137-001 product photo · AFL catalogue, page 166.B3P456-EC137-001B3P456-EC137-001: review equipment cooling fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
Fan-wall impeller · AFL equipment presentation, slide 17.B3P640-EC188-901B3P640-EC188-901: review equipment cooling fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
B3P225-EC072-008 product photo · AFL catalogue, page 92.B3P225-EC072-008B3P225-EC072-008: review equipment cooling fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
EC axial fan · AFL equipment presentation, slide 19.A3P500-EC102-008A3P500-EC102-008: review equipment cooling fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
DC fan · AFL equipment presentation, slide 20.A3P180-DC092-002A3P180-DC092-002: review equipment cooling fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
DC panel fan · AFL equipment presentation, slide 21.A3P200-DC072-027A3P200-DC072-027: review equipment cooling fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
Enclosed DC fan · AFL equipment presentation, slide 22.B3P225-DC072-903B3P225-DC072-903: review equipment cooling fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
B456 installation drawing · AFL equipment presentation, slide 24.B3P456-EC137-950B3P456-EC137-950: review air-handling unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
Framed B400 configuration · AFL equipment presentation, slide 25.B3P400-EC188-031B3P400-EC188-031: review air-handling unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
Framed B400 configuration · AFL equipment presentation, slide 25.B3P400-EC188-032B3P400-EC188-032: review air-handling unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
B450 impeller illustration · AFL equipment presentation, slide 26.B3P450-EC188-951B3P450-EC188-951: review air-handling unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
B3P355-EC188-024 product photo · AFL catalogue, page 141.B3P355-EC188-024B3P355-EC188-024: review air-handling unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
2 × 4 FFU assembly · AFL equipment presentation, slide 4.B3P310-EC092-016B3P310-EC092-016: review fan filter unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
2 × 4 FFU assembly · AFL equipment presentation, slide 4.B3P310-EC092-019B3P310-EC092-019: review fan filter unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
2 × 4 FFU assembly · AFL equipment presentation, slide 4.B3P310-EC092-045B3P310-EC092-045: review fan filter unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
2 × 4 FFU assembly · AFL equipment presentation, slide 4.B3P310-EC092-040B3P310-EC092-040: review fan filter unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
2 × 4 FFU assembly · AFL equipment presentation, slide 4.B3P310-EC092-041B3P310-EC092-041: review fan filter unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
2 × 4 FFU assembly · AFL equipment presentation, slide 4.B3P325-EC102-002B3P325-EC102-002: review fan filter unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
4 × 4 FFU assembly · AFL equipment presentation, slide 5.B3P400-EC102-048B3P400-EC102-048: review fan filter unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
4 × 4 FFU assembly · AFL equipment presentation, slide 5.B3P400-EC102-065B3P400-EC102-065: review fan filter unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
4 × 4 FFU assembly · AFL equipment presentation, slide 5.B3P400-EC102-067B3P400-EC102-067: review fan filter unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
4 × 4 FFU assembly · AFL equipment presentation, slide 5.B3P400-EC102-070B3P400-EC102-070: review fan filter unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
4 × 4 FFU assembly · AFL equipment presentation, slide 5.B3P400-EC102-075B3P400-EC102-075: review fan filter unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
4 × 4 FFU assembly · AFL equipment presentation, slide 5.B3P400-EC102-095B3P400-EC102-095: review fan filter unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.
4 × 4 FFU assembly · AFL equipment presentation, slide 5.B3P400-EC102-096B3P400-EC102-096: review fan filter unit fan specifications, mounting requirements and technical sources before selecting a fan for your equipment.